See more products
     
  ECPD-3 SERIES Three phase
     
  EC-GT 100KA / 200KA



Diverter protectors  > Three phase  > Submodels: ECP-3 SERIES Three phase
  Connection diagram
..............................................
  print
  pdf product
ECP-3 SERIES Three phase


FOR EXPOSED AREAS
Primary protective devices three phase ECP- Series, diverter type, provide an effective protection against transients and disturbances over the electric power sources, either in Normal Mode (Disturbances between phases or between phase and neutral, also called Differential Mode) or Common Mode (Disturbances between Phase and Ground, and between neutral and Ground). Besides, it attenuates high and low energy transients generated by atmospheric discharges.
ECP- Series filters act as primary protectors, complying with B and C categories according to IEEE C6241 normative.



Characteristics
Current Dicharge
from 40 to 100KA, wave 8/20Áseg.

State & failure indicator
Stat ( Blue led), Failure: (Red led)

Remote alarm
NA/NC dry contacts - (Optional)

Warranty
5 years
 

Technical Specification

Connection
Parallel

Operating Current
220/380VCA +/- 20%

Operating frecuency
47- 63Hz.

Discharge current capability
40 -80 -100KA (wave 8/20Áseg)

Electrical Configuration
WYE - Star Triphasic

Models
ECP-3-40KA / ECP-3-80KA / ECP-3-100KA

Response Time
<5 nanosecs.

Operating temperature
-40 a + 60░C

Humidity
5% to 85% Non condensed

Cabinet
Reinforced metal, ready for outdoor installation.

Weight
10 Kg

Measures
380 x 380 x 210 mm


............................................................................................................................................................